15A NCAC 02U .0701. SETBACKS
-
(a) Treatment and storage facilities associated with systems permitted under this Subchapter shall adhere to the setback requirements in 15A NCAC 02T .0500 except as provided in this Rule.
(b) Final effluent storage facilities shall meet all setback requirements for riparian buffer rules pursuant to 15A NCAC 02B as well as the following setbacks:
feet
Any private or public water supply source 100
Surface waters (streams – intermittent and perennial, perennial waterbodies,
and wetlands) 50
Any well with exception of monitoring wells 100
Any property line 50
Otherwise storage facilities shall meet the provisions of Paragraph (a) of this Rule.
(c) The setbacks for utilization areas where reclaimed water is discharged to the ground shall be as follows:
feet
Surface waters (streams – intermittent and perennial, perennial waterbodies,
and wetlands) not classified SA 25
Surface waters (streams – intermittent and perennial, perennial waterbodies,
and wetlands) classified SA 100
Any well with exception to monitoring wells 100
(d) No setback between the application area and property lines is required.
History Note: Authority G.S. 143-215.1; 143-215.3(a);
Eff. June 18, 2011.