15A NCAC 18C .0801. CAPACITIES: DETERMINING MINIMUM EFFECTIVE VOLUME  


Latest version.
  • The minimum effective volume of pressure tanks, in gallons, shall equal the peak demand, in gallons per minute, minus the pumping capacity (gpm), multiplied by 20.

     

History Note:        Authority G.S. 130A‑315; 130A‑317; P.L. 93‑523;

Eff. January 1, 1977;

Readopted Eff. December 5, 1977.